Guangzhou GENY Electric Company
|
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Technical Speciation |
|
Number Of Meter Positions |
3 / 6 |
Accuracy Class |
0.01% / 0.02% |
Power Source |
YCS-103-X |
Reference Standard Meter |
GENY: SZ03A-K8 RADIAN: RD33-233 ZERA: COM3003 EMH/MTE: K2006 |
Scanning Head |
YCG-S Series |
Voltage |
|
Test voltage output(Phase-Neutral) |
3x(40V~500V)(or customized) |
Power of the voltage output |
3x200VA |
Resolution |
Better than 0.001% of full scale value of range |
Stability |
Better than 0.002% /h (integration time 150s) |
Load regulation from 0~max. load |
Better than 0.01% |
Distortion factor |
Better than 0.05% for linear resistance load |
Harmonic |
2nd~21st free programmable |
Current |
|
Test current output |
3x (1mA~120A) max. to 230A |
Power of the current output |
3x300VA |
Resolution |
Better than 0.001% of full scale value of range |
Stability |
Better than 0.002% /h (integration time 150s) |
Load regulation from 0~max. load |
Better than 0.01% |
Distortion factor |
Better than 0.05% for linear resistance load |
Harmonic |
2nd~21st free programmable |
Phase angle |
|
Range |
0~360 |
Resolution |
0.01 |
Frequency |
|
Range |
45Hz~65Hz |
Resolution |
0.001Hz |
Error display |
|
Type of error display |
Red LED |
Resolution of error displays |
8 digitals |
Other |
|
Voltage supply |
3x220/380V±10%(or customized) 50/60Hz ±2Hz |
Ambient temperature |
-10°C~+40°C |
Relative humidity |
35%~85% |
Description: