Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Measurement accuracy |
high voltage current 1% |
|
low voltage current 0.5% |
||
ratio 1% |
||
angle:±5° |
||
Measurement range of ratio |
1~300 |
|
Current range |
high voltage clamp |
200A, 500A, 600A |
Low voltage clamp |
5A |
|
Without obstacles, high voltage clamp transmitting distance |
150 meters |
|
Maximum wire diameter |
High voltage clamp |
Φ400mm |
5A Clamp |
Φ8mm |
|
Toleration voltage |
15kV/min |
|
Entire instrument power consumption |
<3VA |
|
Frame size |
195*100*45mm |
|
Weight |
0.5kg |
YCCTR-9901 High-voltage current transformer turn,-ratio test set is designed for on-line testing turns ratio of the current transformers of not more than 10kV. It consists of a high-voltage clamp-type CT and a handheld testing unit.
The high-voltage clamp-type CT installed on the end of a high-voltage insulation operating rod, is used to test the high-voltage current of current transformers. The handheld testing unit composed of a meter and a low-voltage clamp-type CT, is used to test the low-voltage current of the current transformers. The high-voltage clamp-type CT sends the collected current signal to the handheld testing unit through wireless transmission mode, then the handheld testing unit, according to the two current signals (the high-voltage and low voltage), calculates the turns ratio and current magnitude of primary and secondary windings.
The high-voltage clamp-type CT and the handheld testing unit are powered by rechargeable batteries, and work continuously for 8 hours on a single charge. The high voltage insulation operating rod is pull-out structure, its maximum length is 5m, ensuring the safety of operating personnel.
Guangzhou GENY Electric Company [China (Mainland)]
Business Type:Manufacturer
City: Guangzhou
Province/State: Guangdong
Country/Region: China (Mainland)